A non-nuclear fire that came close to mattering: it destroyed enough cabling and cooling to degrade the reactor's safety systems, and the plant never restarted.

The event
Date1989-10-19
INES rating3 Serious incident
Facilitypower reactor
UnitVandellos nuclear power plant 1
Reactor typeGas-cooled reactor (GCR)
CountrySpain
Casualties
Deaths at the time0
Acute radiation deathsnot established

No deaths or injuries, and no radiological release.

Cause

A turbine blade failure started a fire in the turbine hall that damaged cabling and progressively disabled several safety systems.

What happened

A blade failed in one of the turbines, which started a substantial fire in the turbine hall. The fire damaged cable runs, and flooding from firefighting disabled equipment, progressively removing redundant cooling and safety trains.

No radioactivity was released. But the sequence eroded defence in depth in a way that made the margin uncomfortably thin.

Consequences

The regulator required extensive upgrades. The operator judged them uneconomic and shut the plant permanently.

What changed afterwards

Vandellòs is the standard case study for fire as a common-cause failure. A fire is not a nuclear event, but it can take out redundant systems simultaneously because their cables often share routes. Fire protection and cable separation requirements at plants worldwide trace to this accident and to the 1975 Browns Ferry fire in the United States.

Other accidents

AccidentINESDate
Chernobyl 7 1986-04-26
Fukushima Daiichi 7 2011-03-11
Kyshtym (Mayak) 6 1957-09-29
Windscale Pile 1 fire 5 1957-10-10
Three Mile Island Unit 2 5 1979-03-28
SL-1 4 1961-01-03
Saint-Laurent A2 fuel melt 4 1980-03-13
Tokaimura criticality accident 4 1999-09-30
Davis-Besse vessel head corrosion 3 2002-03-06

Sources